Detnov Conventional manual call point
Conventional manual call point
PCD-100
Description
The PCD-100 is a manual call point for conventional detection systems. It is compatible with Detnov's conventional control panels and with addressable modules MAD-441 and MAD-442, and with most of the conventional control panels in the market.
The resettable manual call point PCD-100 has been developed for use in conventional fire detection installations. Once activated, it remains active until a manual reset is performed using the key.
The onventional manual call pointPCD-100 is an essential element for the manual alarm generation in the conventional system. The manual call point is connected directly to the zone (it includes 100 Ω 2W resistance for the alarm level in the conventional system).
Optional cover: TBD-450
Built-in supplement: SMD-450
Features
Resettable manual call point
Includes a key for maintenance test
Includes 100 Ω 2W resistance for the alarm level
EN 54-11 approved
Applications
The resettable manual call point PCD-100 of Detnov allows the immediate manual activation of a fire alarm.
It is one of the basic devices in any fire detection system, since it allows the activation by the user in case of fire, prior to the entry of an alarm of the automatic detection system.
Technical features
|
Manual call point |
|
|
Operating voltage: |
From 9 to 28VDC |
|
Quiescent current consumption: |
<100 μA |
|
Alarm current consumption: |
<100 mA |
|
Connections |
|
|
2 x 1,5 mm² twisted and shielded cable |
|
|
Environment |
|
|
Operating temperature: |
From -10ºC to +50ºC |
|
Relative humidity: |
95% without condensation |
|
IP Index: |
IP30 |
|
Physical features |
|
|
Size: |
98 mm x 98 mm x 48 mm |
|
Material: |
ABS |
|
Approvals |
|
|
EN 54-11 |
|
|
Certificate number: |
0370-CPR-2347 |
Dimensions